Supermarket electrical equipment management
The electrical equipment of large supermarkets mainly includes air conditioning units, air conditioners, water pumps, lighting and fresh power, among which fire pumps, spray pumps, fire shutter doors, smoke exhaust fans and other power supplies related to fire protection are Class I loads, business area lighting, accident lighting and weak current power supplies are Class I loads, escalators are Class II loads, cash register systems, security systems and the rest are Class III loads. Therefore, the regional power supply department is generally required to provide two 10KV power supplies as the main power supply. Two transformers and low-voltage contacts are set in the substation. On this basis, diesel generators can be added as the standby power supply according to the owner's requirements. Diesel generator capacity includes refrigeration equipment, weak current equipment, important processing equipment in fresh food processing area, and equipment used in supermarket logistics system.