10-30KVA High Frequency Online UPS (3:3)
Product Detail
Specification
Applications
Documents
Solution
Jupiter Series 3P/3P High Frequency UPS is the high density version of double-conversion online UPS with a output power factor 0.8. Ranging from 10KVA to 30KVA, it’s designed in small footprints with DSP technology and active input power factor correction design to ensure better output voltage conditions, power quality and power performance at all times. Its dual mains inputs will secure the power reliability in power fluctuation area.
Function Features
1.Online double conversion technology with DSP control
Jupiter series is applied online double conversion technology to effectively insulate against network disturbances and enable higher load uptime. A Digital Signal Processor (DSP) control provides an improved solution with high performance.
2.Output power factor 0.8
Compared to the online UPS in the current market, Jupiter series(PHT3110~PHT3330) high frequency UPS provides better output power factor up to 0.8. It offers higher performance and efficiency for critical applications.
3.ECO mode operation for energy saving
Offers efficiency as high as 97% to cut energy usage and cost. UPS power application via static bypass, timely returning to online double conversion when the need arises.
4.Emergency power off (EPO) function
This feature can secure the personnel and equipment in case of fires or other emergencies.
5.Wide input voltage range(190V-520V)
Jupiter series can still provide stable power to connected devices under unstable power environments.
6.50/60 Hz Frequency Converter Mode
Lock output frequency at 50Hz or 60Hz to suit power sensitive equipments.
Main Features
• DSP technology guarantees high performance
• Output power factor 0.8
• Adjustable battery numbers
• Generator compatible
• Active power factor correction in all phases
• 3-stage extendable charging design for optimized battery performance
• SNMP+USB+RS232 multiple communications
• Optional N+X parallel redundancy
10KVA-30KVA (Three-ins and Three outs) |
|||||||||||
Model |
PHT3310(B) |
PHT3315(B) |
PHT3320(B) |
PHT3330(B) |
|||||||
Capacity |
10KVA/8KW |
15KVA/12KW |
20KVA/16KW |
30KVA/24KW |
|||||||
Phase |
3-phase in / 3-phase out |
||||||||||
Battery Voltage |
192A Default, 192V/240V Selectable |
240V |
|||||||||
Long-run Model |
Size, D X W X H (mm) |
592X250X826 |
815X250X826 |
||||||||
Net Weight (Kgs) |
38 |
40 |
40 |
64 |
|||||||
Standard Model |
Size, D X W X H (mm) |
815X250X826 |
815X300X1000 |
||||||||
Net Weight (Kgs) |
109 |
164 |
164 |
234 |
|||||||
Input | |||||||||||
Input Voltage |
3 x 400 VAC (3-phase+N) |
||||||||||
Voltage Range |
190-520 VAC (3-phase) @ 50% load ; 305-478 VAC (3-phase) @ 100% load |
||||||||||
Frequency Range |
46Hz ~ 54 Hz @ 50Hz 56Hz ~ 64 Hz @ 60Hz |
||||||||||
Power Factor |
≧ 0.99 @ 100% |
||||||||||
Output | |||||||||||
Output voltage |
3 x 400 VAC (3-phase+N) |
||||||||||
AC Voltage Regulation (Batt. Mode) |
± 1% |
||||||||||
Frequency Range (Synchronized Range) |
46Hz ~ 54 Hz @ 50Hz 56Hz ~ 64 Hz @ 60Hz |
||||||||||
Frequency Range (Batt. Mode) |
50 Hz ± 0.1 Hz or 60Hz ± 0.1 Hz |
||||||||||
Current Crest Ratio |
3:1 (Max.) |
||||||||||
Harmonic Distortion |
≦2 % THD (Linear Load); ≦5 % THD (Non-linear Load) |
||||||||||
Transfer Time |
AC Mode to Batt. Mode |
0 ms |
|||||||||
Inverter to Bypass |
0 ms |
||||||||||
Waveform (Batt. Mode) |
Pure Sine Wave |
||||||||||
Efficiency | |||||||||||
AC Mode |
> 90.5% |
> 91% |
> 91% |
> 91.3% |
|||||||
Battery Mode |
> 86% |
> 87% |
> 87% |
> 88% |
|||||||
ECO Mode |
> 96% |
> 96% |
> 96% |
> 96% |
|||||||
Battery | |||||||||||
Long-run Model |
Battery Type |
Depending on applications |
|||||||||
Battery Numbers |
16Pcs(16-20Pcs adjustable) |
20Pcs |
|||||||||
Charging Current(Max.) |
4A |
4A |
4A |
12A |
|||||||
Charging Voltage |
273 VDC ± 1% |
||||||||||
Standard Model |
Battery Type |
12V 9AH |
|||||||||
Battery Numbers |
16pcs (16-20 adjustable) |
16pcs (16-20 adjustable)X2 strings |
20pcsX3 strings |
||||||||
Typical Recharge Time |
9 hours recover to 90% capacity |
||||||||||
Charging Current(Max.) |
1A |
2A |
2A |
4A |
|||||||
Charging Voltage |
273 VDC ± 1% |
||||||||||
Display |
|||||||||||
LCD Display |
UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, Fault conditions |
||||||||||
Warning Sound |
|||||||||||
Battery Mode |
Sounding every 4 seconds |
||||||||||
Low Battery |
Sounding every second |
||||||||||
Overload |
Sounding twice every second |
||||||||||
Fault |
Continously sounding |
||||||||||
Environment |
|||||||||||
Temperature and Humidity |
0-95 % RH @ 0- 40°C (Non-condensing) |
||||||||||
Operation Altitude |
<1000m |
||||||||||
Acoustic Noise Level |
Less than 60dB @ 1 Meter |
Less than 65dB @ 1 Meter |
|||||||||
Management | |||||||||||
Smart RS-232 or USB |
Windows® 2000/2003/XP/Vista/2008、Windows® 7/8、Linux、Unix、MAC |
||||||||||
Optional SNMP |
Power management from SNMP manager and web browser |
Remarks:Products specifications are subject to change without notice.
Government Department
Bank Securities
Office Automation
Precision Instrument And Equipment
Server Room
Scientific Research Institutions
Medical Equipment
Industrial Automatic